Indoor:outdoor ratio calculator

Divide the indoor total by the same-day outdoor control to get the ratio an air sample is actually read by — then confirm the reading against the genus split.

spores/m³

Total indoor spore count from the air sample.

spores/m³

Same-day, same-equipment outdoor reference.

Indoor : outdoor ratio0.75
At or below 1 — indoor air carried fewer total spores than outdoors, which generally argues against an indoor source. Still read the genus split: a water-damage indicator (Stachybotrys, Chaetomium) elevated indoors is a finding even with a low total.

How to read the indoor:outdoor ratio

The ratio is indoor total spores/m³ divided by the same-day outdoor total. A value at or below 1 means indoor air carried fewer total spores than outdoors, which generally argues against an indoor source; a value meaningfully above 1 — especially with genera scarce outside — points toward an indoor source. There is no published numeric pass/fail: the EPA and CDC set no acceptable airborne mold concentration, so the ratio is a reading, not a verdict.

The total can mislead. A favorable ratio below 1 can still hide a water-damage signal if a genus that is rare outdoors — Stachybotrys or Chaetomium — is elevated indoors. Always read the per-genus comparison alongside the number. For the full interpretation logic, the indicator-species traps, and why the same-day control is mandatory, see interpreting indoor:outdoor ratios.

Related reading

Sources

Write the report in minutes, not hours.

MoldMind turns your field notes, photos, and lab results into a standards-compliant report you review and approve. Try MoldMind free — 3 jobs, no card.